After installation, flushing and testing - and prior to operation - the geothermal heat pump system should be evaluated using a checkout procedure.
Follow the heat pump manufacturer's checkout list, which usually include the steps outlined in the links below:
This can be done using one of two methods - a calibrated flow meter or the pressure drop method. If the latter is used:
For example, a three-ton heat pump should have about six to nine gpm flow for correct operation.
During heating operation, this should be between 25 to 80 degrees. During cooling operating, it should be between 40 and 110 degrees.
Once it has been determined that the flow rate and entering water temperature are acceptable, the heat pump is ready to be turned on and checked for correction operation.
With the thermostat fan position "on," the blower should start.
In the cooling mode, there should be about a 10 degree difference between the entering and leaving water temperatures. The entering and leaving air temperature difference should be about 16-20 degrees.
In the heating mode, there should be a four to eight degree difference in water temperature. The air temperature difference should be about 25-35 degrees.
Check to see that the emergency heat - if installed, operates.